Technical information
Applications
Industries
Downloads

PowerHeat (AHT) Constant Wattage Heating Cable is engineered for the most demanding environments: combining high power output with extreme mechanical strength thanks to its aluminium sheath, and exceptional thermal resistance up to 500 °C — a world record for a cut-to-length heating cable.

The AHT heating cable is available in 15, 30, 50, 70, 100 and 150 W/m ratings.

Product Specification – Maximum Exposure Temperature: 500 °C

Maximum Allowable Exposure Temperature

500 °C

Maximum Operating Temperature (Energized)

350 °C Refer to the temperature data of the item to be heated

Minimum Operating Temperature

-40 °C

Power Supply

12 à 277 VCA

Cable Dimensions

AHT : 10,7 x 7,7 mm ± 0,5 mm

Minimum Installation Temperature

-40 °C

Minimum Bending Radius

AHT : 50 mm

Weight (kg/100 m)

AHT : 16,5 kg

Cable Gland Thread Size

AHT : M20

 

Maximum Circuit Length (m)

Product Reference

115V

230V

15 AHT

59

118

30 AHT

42

83

50 AHT

32

64

70 AHT

26

54

100 AHT

23

46

150 AHT

19

37

For a voltage drop variation of 10%

Maximum Equipment Operating Temperature (°C)

Nominal Heating Power (W/m)

AHT

15 AHT

350

30 AHT

323

50 AHT

276

70 AHT

140

100 AHT

140

150 AHT

36

Surface Temperature Limits in accordance with EN 50014*

PowerHeat (AHT) Constant Wattage Heating Cable is ideally suited for freeze protection and process temperature maintenance of pipelines and vessels, even under extreme conditions.

Application Example:
Instrumentation and sampling lines must be maintained at optimal temperatures to ensure the reliability of data analysis.

Problem Example:
When exposed to temperatures above 250 °C (e.g. high-pressure steam), most self-regulating heating cables suffer damage. Mineral Insulated (MI) cables are often used in such applications, but they are factory-terminated, involve long lead times, and are complex to install on site.

The Solution – AHT

The AHT heating cable is a high-temperature constant wattage system offering:

-Withstand capability up to 500 °C (350 °C energized) without damage,

-Cut-to-length flexibility on site, ideal for installations with variable routing,

-Easy connection with junction kits or connection boxes,

-Minimum circuit length of 1 m, directly compatible with standard supply voltages (e.g. 230 V), unlike MI cables.

The AHT heating cable provides a flexible, fast-to-install and reliable alternative for temperature maintenance of instrumentation lines in extreme environments.

PowerHeat AHT Constant Wattage Heating Cables are applied across a wide range of industries, including:

-Chemical & petrochemical facilities

-Power generation and thermal power plants

-Metallurgical and steel industries

-Outdoor industrial installations and heavy process applications

-Machinery and equipment manufacturers

-Food & beverage industry

-General industrial sectors

This list is not exhaustive.

Constant Wattage Heating Cable Range