Technical information
Applications
Industries
Downloads

PowerHeat (PHT) constant wattage heating cables offer outstanding power and reliability. Designed for demanding industrial applications, they withstand high temperatures and corrosive environments, and can be easily installed on site.

Product Specification – Maximum Permissible Temperature: 285 °C (545 °F)

Technical Specifications

Maximum allowable temperature

285 °C (545 °F)

Maximum operating temperature under voltage

275 °C (527 °F) Refer to the temperature data of the room to be heated

Power supply

12 à 277 VCA

Cable dimensions

-PHT-N : 10,2 x 7,1 mm ± 0,5 mm

-PHT-NF : 11,1 x 8,0 mm ± 0,5 mm

Minimum installation temperature

-40 °C (-40 °F)

Minimum bending radius

-PHT-N : 45 mm

-PHT-NF : 50 mm

Weight (kg/100 m)

-PHT-C : 9,0 kg

-PHT-CF : 11,0 kg

Cable gland

-PHT-N : M20

-PHT-NF : M20

Maximum circuit length (m)

Product reference

115V

230V

30 PHT

46

88

50 PHT

35

68

70 PHT

30

56

For a voltage drop variation of 10%*

Maximum temperatures of the room to be heated (°C)

Nominal heating power (W/m)

PHT-N

PHT-NF

30 PHT

234

243

50 PHT

186

201

70 PHT

125

147

Surface temperature limits in accordance with standard EN 50014*

Please contact us for any specific requirements.

PowerHeat (PHT) constant wattage heating cable is ideal for temperature maintenance and frost protection of pipes and tanks, even in hazardous or corrosive areas. Easily adjustable to installation lengths, it effectively replaces mineral insulated (MI) cables in industrial heating circuits.

The PowerHeat PHT constant wattage heating cables are used in the following sectors:

-Chemical and petrochemical industries

-Machinery manufacturing

-Power generation and steam networks

-Industrial fluid processing and storage

-Food and beverage industry

-General industries

This list is not exhaustive.

Constant Wattage Heating Cable Range